Produk

Control Module FCM-1 Notifier.

Spesifikasi Control Module FCM-1 Notifier

Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 350 μA direct poll, 375 μA group
poll with LED flashing, 485 μA Max. (LED flashing, NAC
shorted.)

Maximum NAC Line Loss: 4 VDC.
External supply voltage (between Terminals T10 and
T11): Maximum (NAC): Regulated 24 VDC; Maximum
(Speakers): 70.7 V RMS, 50W.
Drain on external supply: 1.7 mA maximum using 24 VDC
supply; 2.2 mA Maximum using 80 VRMS supply.
Max NAC Current Ratings: For class B wiring system, the
current rating is 3A; For class A wiring system, the current rating is 2A.

control module fcm 1 notifier
Control Module FCM-1 Notifier Feature

• Built-in type identification automatically identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire
SLC loop. The FCM-1(A) module requires power (for horns,
strobes, etc.), or audio (for speakers).
• Integral LED “blinks” green each time a communication is
received from the control panel and turns on in steady red
when activated.
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI).
• The FCM-1(A) may be used to switch 24-volt NAC power,
audio (up to 70.7 Vrms).
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease.
• Direct-dial entry of address 01– 159 for FlashScan loops,
01 – 99 for CLIP mode loops.
• Speaker, and audible/visual applications may be wired for
Class B or A (Style Y or Z).

Fungsi Control Module FCM-1 Notifier

FCM-1(A) Control Module: adalah Addressable Control Module yang terhubung ke Notifier intelligent fire alarm control panels yang memiliki fungsi untuk aktivasi perangkat audio visual (horns, strobes, speakers, etc.). hal ini memungkinkan FCM-1(A) untuk aktif secara manual maupun melalui panel alarm saat melakukan pengetesan drill. modul ini telah lulus uji dan sertifikasi badan Internasional seperti UL, ULC, FM Approved, CSFM dan MEA.  masing-masing FCM-1 Notifier menggunakan satu alamat addres untuk pemakaian di panel.

Produk Patigeni

Pressure Reducing Valve PRV Standar UL Cla-Val memiliki 2 tipe yaitu Cla-Val 90G-21 (globe) & 90A-21 (angle)….

NFS2-3030 Intelligent Addressable Fire Alarm System Notifier merupakan control panel yang di desain untuk fasilitas…