Master Control Fire Alarm Secutron

Spesifikasi Master Control Fire Alarm Secutron

  • Listed to UL 864, 9th edition
  • MR-2100 provides a Single Addressable Input Signaling Line Circuit (SLC) for up to 198 Addressable Devices
  • MR-2200 provides Dual Addressable Input Signaling Line Circuits for up to 396 Addressable Devices
  • SLCs are selectable for either Class A (Style 6) or Class B (Style 4) operation
  • Two Notification Appliance Circuits (NACs), Class A (Style Z) or Class B (Style Y); expandable to eight  NACs with optional MRNC2 modules
  • Four programmable functions relays, Form C; expandable to sixteen relays with MRRL4 modules
  • Programmable cross-zoning functions, day/night mode, and selective control operations
  • Two aux. power outputs, 500 mA @ 24 VDC each
  • 6.0 A Power supply with integral battery charger provides 2.5 A for NACs and Auxiliary Outputs; Expandable to provide up to 7 A NAC Current
  • Four additional communications ports for Dialer, PC Interface, Voice Evacuation System, and Remote Annunciators
  • Optional Style 7 (DCLR) MR network peer-to-peer communications
    LCD/LED system status display with optional MRLD8 LED zone display modules (required for ULC listed applications)
  • Surface/flush mount cabinet with dead front construction allows up to 12 Ah batteries internally mounted
  • Battery charger is capable of charging up to 35 Ah mounted in an external battery cabinet
  • Cabinet doors are removable for easy installation
  • Terminal blocks are removable for easy wiring
  • Operating program and database can both be uploaded/downloaded using a Windows® based PC with Secutron Programming Software
  • Non-volatile event history log stores 1000+ events

Master Control Fire Alarm Secutron Addressable 1 loop 2 loop

Secutron's MR-2100 and MR-2200 addressable input fire alarm control panels provide flexible and cost effective operation to satisfy system requirements for both economy and capability. Their modular design assures that as system needs and applicable codes evolve, fire alarm control panel functions can be updated as required. Optional networking modules allows the MR-2100 and MR-2200 to be connected to a Secutron network to provide additional input circuits, visual zones, programmable notification appliance (bell) circuits, and relays. Up to 254 control and annunciator units can be networked together. The network is a DCLR (Data Communications Link, Redundant) configuration loop.

Master Control Fire Alarm Secutron Addressable 3 loop MR-2351-LD-RA

Single intelligent SLC Loop that supports 126 points.
Expandable to 378 points with ALC-252 Dual Loop Controller Module
• Points can be any combination of Intelligent Sensors or Modules
• Supports Photoelectric Sensors, Variable Heat Sensors and Multi–Sensor (Heat/Photo)
• Equipped with 2 line by 20 character back-lit LCD display, numerical keypad and an integrated UDACT/ Digital Communicator
• LCD display allows for 32 characters to be confiured for user defied messages
• Digital Communicator can be confiured for DACT or UDACT mode of operation
• Space for up to 64 zones of LED annunciation with optional RAX-332 programmable LED annunciator
• Confiurable via the front panel, PC Confiurator, or remote dial up through the built-in modem
• Sensors can be confiured as Alarm, Verifid Alarm, Latching or Non-Latching Supervisory, Monitor and Trouble-Only
• Modules can be configured as Alarm, Latching Supervisory, Non-Latching Supervisory, Water Flow, Monitor, Trouble, Fire Drill Switch, Signal Silence Switch,
Aux Disconnect Switch and Buzzer Silence Switch
• Base panel is equipped with Four Class “B” (Style “B”) indicating circuits which may be confiured as Class “A” (Style “Z”) using a Class “A” signal converter module
• Indicating Circuits may be confiured as Silenceable or Non-Silenceable for both signals and strobes
• Built-in sync protocols for the following strobe manufacturers: Mircom, Amseco, System Sensor, Gentex, Faraday and Wheelock
• Relay contacts for Common Alarm, Auxiliary/ Alarm (Disconnectable), Common Supervisory and Common Trouble
• Confiurable Signal Silence Inhibit, Auto Signal Silence and One-Man Walk Test
• Subsequent Alarm, Supervisory, and Trouble operation
• RS-485 Interface for Remote LED and LCD Annunciators
• Positive Alarm Sequence
• Two event history logs comprised of a 200 event alarm log for alarm related events and a 200 event general log for all other events
• 5.5 Amp Power Supply
• Optional City Tie/Polarity Reversal module

Master Control Fire Alarm Secutron Addressable 5 loop MMX-2003-12NDS

Fire Alarm Control
• One expandable to nine Intelligent Signaling Line Circuits (SLC)
• Modular design
• Each SLC Loop is capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be wired in Style 6 or 7 (Class A) or Style 4 (Class B)
• Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each
• Large 4 by 20 character Back-lit LCD Display with user friendly menu
• Supported languages: English, French, Arabic* and Hebrew* (*960 character back-lit LCD display only)
• Correlatable Switch Inputs which allow for multifunctional outputs
• Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor
• Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble
• Group bypass with built-in false alarm prevention technology
• RS-232 output for remote system printer or CRT
• Two Event History Logs comprised of a 6000 event alarm history log for alarm related events and a 6000 event log for all events
• Supports three confiuration fies (current, previous and next confiuration) with “hot swap” support
• Supports Conventional Hardwire Adder Modules
• Built-in One Man Walk Test operation
• Confiurable for Canadian Two Stage operation
• Confiurable for Coded Operation
• Capability to adjust Intelligent Smoke Detector sensitivity levels
• Real time 3D graphical monitoring and control using Open Graphic Navigator™
• BACnet support
• Supports Boolean logic functions
• Built-in Ethernet port
• Remote diagnostics via a built-in web server
• UL listed for Smoke Control

Master Control Fire Alarm Secutron Konvensional 5 Zone

  • Listed to UL 864, 9th edition
  • 5 Style B (Class 'B') dual-use zones
  • 2 Style Y (Class 'B') notification appliance circuits
  • 6 Amp power supply
  • 500mA of Aux. power
  • Common alarm relay
  • Common trouble relay
  • Integral battery charger
  • 'Secur-Bus' for dialer and remote annunciation
  • Event buffer
  • Six programmable zone options
  • Class A capability, both NAC and Zones
  • One-man walk test
  • Programmable NAC silence timer
  • 3 LEDs per zone
  • Front panel programming

Master Control Fire Alarm Secutron Konvensional 10 Zone

Features
• Listed to UL 864, 9th edition• Available in six and twelve zone models
• Available in LED and LCD Display confiurations
• LCD Display versions are equipped with a 2 line by 20 character back-lit LCD display and numerical keypad
• Integrated UDACT/Digital Communicator on select models
• Front panel and PC programmable
• LED Display versions are front panel (using CFG-300 confiuration tool) and PC programmable
• Remote upload/download capabilities
• Base panel is equipped with Class “B” (Style “B”) initiating circuits which may be confiured as Class “A” (Style “D”) using a Class “A” converter module
• Initiating circuits may be confiured as Alarm, Verifid Alarm, Waterflw Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Monitor and TroubleOnly
• Base panel is equipped with Class “B” (Style “Y”) indicating circuits which may be confiured as Class “A” (Style “Z”) using a Class “A” signal converter module
• Audible signals may be configured for Steady, Temporal Code, California Code and March Time
• Indicating Circuits may be confiured as Silenceable or Non-Silenceable for both signals and strobes
• Built-in sync protocols for the following strobe manufacturers: Mircom, Amseco, System Sensor, Gentex, Faraday and Wheelock
• Relay contacts for Common Alarm, Auxiliary/Alarm (Disconnectable), Common Supervisory and Common Trouble
• Configurable Signal Silence Inhibit, Auto Signal Silence and One-Man Walk Test
• Subsequent Alarm, Supervisory, and Trouble operation
• RS-485 Interface for Remote LED Annunciators, LCD Annunciators and Remote Smart Relay Modules
• Two event history logs comprised of a 200 event alarm log for alarm related events and a 200 event general log for all other events
• 5 Amp Power Supply
• Optional modules for additional internal relay circuits and City Tie/Polarity Reversal
• Optional trim rings for semi-flsh mounting