Smoke Detector Simplex

Spesifikasi Smoke Detector Simplex

Voltage 15 to 32 VDC from Fire Alarm Control Panel IDC
Standby Current 100 μ A @ 24 VDC
Alarm Current, 2-Wire Operation Up to 86 mA maximum, exact current is determined by alarm current limiting of connected IDC
Alarm Current, 4-Wire Operation 24 mA typical @ 24 VDC Auxiliary Relay Ratings Refer to page 2 under Product Selection
Air Velocity Range 0-2000 ft/min (0-610 m/min)
UL Listed Temp. Range 32° to 100° F (0° to 38° C)
Operating Temp. Range 15° to 122° F (-9° to + 50° C)
Humidity Range 10% to 95% RH from 32° to 122° F (0° to 50° C) non-condensing
Color Frost White
Dimensions 4-7/8” Dia. x 1-7/8” H, mounted in base (124 mm x 48 mm); refer to page 3 for detail

Photoelectric Smoke Detector Simplex 4098-9601 TrueAlarm

Photoelectric smoke detector with on-board
TrueAlarm sensitivity drift compensation
Functional chamber enclosure:
• Louvered design enhances smoke capture by directing flow to chamber
• Entrance areas are minimally visible when ceiling mounted
Multi-function indicator LED indicates normal and alarm conditions
Magnetically operated functional test:
• Initiates alarm and verifies performance
• Identifies general sensitivity status using detector LED Models available in two sensitivity settings:
• 4098-9601, Standard Sensitivity, nominal 2.8%/ft obscuration*
• 4098-9605, Special Application Sensitivity, nominal 3.5%/ft obscuration
Available options:
• Bases for 2-wire or 4-wire operation
• Auxiliary alarm relay output
• Remote alarm indicating LED
Designed for EMI compatibility
UL listed to Standard 268

Photoelectric Smoke & Heat Detector 4098-9602 TrueSense

TrueAlarm detection with TrueSense operation
**
combines photoelectric detection with heat detection to provide a multi-mode detector with four detection mechanisms:
• Stable and reliable photoelectric smoke detection with built-in TrueAlarm sensitivity drift compensation
• Resettable, thermistor-based fixed temperature detection
• Resettable, thermistor-based rate-of-rise temperature detection
• And TrueSense detection, a patented correlation of smoke activity and thermal activity providing intelligent fire detection earlier than with either activity alone**
Functional chamber enclosure:
• Louvered design enhances smoke capture by directing flow to chamber
• Entrance areas are minimally visible when ceiling mounted Multi-function LED indicator:
• Indicates normal and alarm conditions
• Provides status during magnetic functional test
Magnetically operated functional test:
• Initiates alarm and verifies performance
• Identifies general sensitivity status using detector LED pulses (normal, more sensitive, or less sensitive)
• With detectors categorized as normal or needing cleaning or other service, maintenance priorities can be more easily determined
Available options:
• Bases for 2-wire or 4-wire operation
• Auxiliary alarm relay output
• Remote alarm indicating LED

Fungsi Smoke Detector Simplex

Smoke Detector Simplex akan mendeteksi asap kebakaran dengan baik. Perangkat ini akan memberikan input berupa sinyal elektrik yang akan diteruskan ke panel kontrol. Dari panel kontrol, sistem akan aktif sehingga dapat memperingatkan para penghuni gedung untuk segera mengambil tindakan pemadaman atau melakukan evakuasi, baik barang maupun diri. Fire alarm akan membantu melakukan identifikasi kebakaran sejak dini, baik melalui detektor asap atau panas.