Zone Module for Detector FZM-1 Notifier

Spesifikasi Zone Module for Detector FZM-1 Notifier

 Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 ohms.
Average operating current: 300 μA, 1 communication and 1
LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.

 

Zone Module for Detector FZM-1 Notifier


• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power
source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops,
01 – 99 on CLIP loops.
• LED flashes during normal operation; this is a programmable
option.

LED latches steady to indicate alarm on command from control panel.
The FZM-1(A) Interface Module is intended for use in intelligent, addressable systems,
where the individual address of each module is selected using built-in rotary switches.
This module allows intelligent panels to interface and monitor twowire conventional
smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional
detectors back to the control panel. All two-wire detectors being monitored must be UL compatible
with the module. The FZM-1(A) can be used to replace MMX-2(A) modules in existing systems.

Fungsi Zone Module for Detector FZM-1 Notifier

FZM-1 Notifier merupakan sebuah modul yang dapat merubah inputan dari detektor kebakaran menjadi address / alamat agar dapat dibaca melalui panel Addressable Notifier. Zone module ini FZM-1(A) merupakan standart module yang dapat memonitor two wire detector compatible konvensional seperti SD-651 atau 5601, bekerja dengan aliran listrik 24 volt DC, dan mampu mencover maksimal 30 detektor untuk 1 zonanya. masing-masing pengalamatan pada FZM-1 Notifier module ini menggunakan rotary switch yang harus diatur secara manual mengikuti desain alamat yang direncanakan. sinyal yang ditransmisikan berupa normal, open atau alarm.

Produk Patigeni