Control Panel Suppression System Notifier RP2002

Spesifikasi Control Panel Suppression System Notifier RP2002

Electrical Specifications

  • RP-2002 (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66 amps
  • RP-2002E (FLPS-7 Power Supply): 240 VAC, 50/60 Hz, 2.085 amps
  • Wire size: minimum 14 AWG (2.0 mm²) with 600 V insulation, supervised, nonpower-limited
  • Cabinet Specifications
    Door: 19.26" (48.92 cm) high x 16.82" (42.73 cm) wide x
    0.72" (1.82 cm) deep. Backbox: 19.00" (48.26 cm) high x
    16.65" (42.29 cm) wide x 5.25" (13.34 cm) deep. Trim Ring
    (TR- CE): 22.00" (55.88 cm) high x 19.65" (49.91 cm) wide.
  • Shipping Specifications
    Weight: 24.05 lbs. (10.9 kg)
  • Dimensions:
    – Height 20.00" (50.80cm)
    – Width 22.50" (57.15cm)
    – Depth 8.50" (21.59cm)
  • Temperatur dan rentang kelembaban
    System ini memenuhi standart NFPA yg bekerja pada suhu 0 – 49°C/32 – 120°F dan kelembaban 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). Masa Hidup baterai dipengaruhi suhu yang bervariasi bahkan sampai extrim, namun kami sarankan untuk penggunaan Panel ditempatkan pada suhu ruangan of 15 – 27°C/60 – 80°F.
  • NFPA Standards
    The RP-2002(E) complies with the following NFPA 72 Fire
    Alarm Systems requirements:
    – NFPA 12 CO2 Extinguishing Systems
    – NFPA 12A Halon 1301 Extinguishing Systems
    – NFPA 12B Halon 1211 Extinguishing Systems
    – NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)
    – NFPA 2001 Clean Agent Fire Extinguishing Systems

Suppression Release Control Panel RP2002 Notifier Feature

• Listed to UL Standard 864, 9th edition.
• FM Approved.
• Designed for agent releasing standards NFPA 12, 12A, 12B, and 2001.
• Meets International Building Code (IBC) seismic requirements.
• Disable/Enable control per input zone and output zone.
• Extensive transient protection.
• Dual hazard operation.
• Adjustable pre-discharge, discharge and waterflow delay timers.
• Cross-zone (double-interlock) capability.
• Six programmable Style B (Class B) IDCs (Initiating Device
Circuit).
• System Sensor i3 series detector compatible.
• Four programmable Style Y (Class B) output circuits - (special application power).
• Strobe synchronization:
– System Sensor
– Wheelock
– Gentex
– Faraday
– Amseco
• Three programmable Form-C relays.
• 7.0 amps total 24 VDC output current.
• Resettable and non-resettable output power.
• Built-in Programmer.
• ANN-BUS connector for communication with optional
devices (up to 8 total of any of the following):
– N-ANN-80 Remote LCD Annunciator
– N-ANN-I/O LED Driver
– N-ANN-S/PG Printer Modules
– N-ANN-RLY Relay Module
– N-ANN-LED Annunciator Module
• 80-character LCD display (backlit).
• Real-time clock/calendar with daylight savings time control.
• History log with 256 event storage.
• Piezo sounder for alarm, trouble and supervisory.
• 24 volt operation.
• Low AC voltage sense.
• Outputs Programmable for:
– Releasing Circuits or NACS
• NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Non-silenceable
– Release Stage Sounder
Page 2 of 4 — DN-60240:C3 • 3/6/2017
• Automatic battery charger with charger supervision.
• Optional Dress Panel DP-51050 (red).
• Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet.
• Optional N-CAC-5X Class A Converter Module for Outputs and IDCs.
• Optional 4XTM Municipal Box Transmitter Module.
• Optional Digital Alarm Communicators (411, 411UD, 411UDAC).
• Optional ANN-SEC card for a secondary ANN-BUS.

D4120 Duct Smoke Detector System Sensor

Fungsi Control Panel Suppression System Notifier RP2002

RP-2002 adalah Panel Suppression yang dapat merilis untuk aplikasi system tunggal maupun ganda. RP-2002  dapat diandalkan dengan menggunakan deteksi kebakaran terintegrasi. Panel ini sangat cocok digunakan untuk perlindungan bangunan komersial, industri serta bangunan institusional yang membutuhkan pelepasan berbasis agen. RP-2002 kompatibel dengan detektor i3 System Sensor yang merupakan detektor asap konvensional yang dapat mengirimkan sinyal masalah pemeliharaan ke FACP yang menunjukkan perlunya pembersihan dan sinyal ‘freeze’ saat suhu turun di bawah 45 ° F (7,22 ° C). Selain itu, panel kontrol kompatibel dengan perangkat input konvensional seperti detektor asap dua kawat, detektor asap empat kawat, manual button, perangkat aliran air (flow switch), tamper switch dan perangkat kontak lain yang menggunakan kondisi default normally open (NO).

Empat output dapat diprogram sebagai NAC (Notification Appliance Sirkuit) atau melepaskan sirkuit. Tiga program Relay Formulir-C (dari pabrik diprogram untuk Alarm, identifikasi masalah, dan pengawasan) serta 24 VDC aplikasi khusus reset. RP-2002 menganalisa semua kabel, tegangan AC, pengisi daya baterai dan tingkat baterai. Aktivasi detektor asap yang kompatibel menjadi perangkat inisiasi alarm kebakaran yang mengaktifkan audible dan visual,
memberi sinyal perangkat, menerangi indikator, menampilkan informasi alarm pada panel LCD, membunyikan sounder di FACP, mengaktifkan relay alarm FACP dan operasikan opsional modul yang digunakan untuk memberi tahu stasiun jarak jauh atau memulai bantuan fungsi kontrol.